CAD32P7
SPECIFICATIONS:
Range |
TeSys TeSys Deca |
Product name |
TeSys CAD |
Product or component type |
Control relay |
Device short name |
CAD |
Contactor application |
Control circuit |
Utilisation category |
DC-13 AC-15 AC-14 |
Pole contact composition |
3 NO + 2 NC |
[Ue] rated operational voltage |
<= 690 V AC 25...400 Hz |
Control circuit type |
AC at 50/60 Hz |
[Uc] control circuit voltage |
230 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947 |
[Ith] conventional free air thermal current |
10 A (at 60 °C) |
Irms rated making capacity |
140 A AC conforming to IEC 60947-5-1 250 A DC conforming to IEC 60947-5-1 |
[Icw] rated short-time withstand current |
100 A - 1 s 120 A - 500 ms 140 A - 100 ms |
Associated fuse rating |
10 A gG conforming to IEC 60947-5-1 |
[Ui] rated insulation voltage |
600 V UL certified 600 V CSA certified 690 V conforming to IEC 60947-5-1 |
Mounting support |
Rail Plate |
Connections - terminals |
Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end |
Tightening torque |
1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
Control circuit voltage limits |
0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
Operating time |
12...22 ms coil energisation and NO closing 4...12 ms coil de-energisation and NO opening 4...19 ms coil energisation and NC opening 6...17 ms coil de-energisation and NC closing |
Mechanical durability |
30 Mcycles |
Maximum operating rate |
180 cyc/mn |
Inrush power in VA |
70 VA 50 Hz (at 20 °C) |
Hold-in power consumption in VA |
8 VA 50 Hz (at 20 °C) |
Minimum switching voltage |
17 V |
Minimum switching current |
5 mA |
Non-overlap time |
1.5 ms on energisation between NC and NO contact 1.5 ms on de-energisation between NC and NO contact |
Insulation resistance |
> 10 MOhm |
Mechanical robustness |
Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
Height |
77 mm |
Width |
45 mm |
Depth |
84 mm |
Net weight |
0.58 kg |
Standards |
EN/IEC 60947-5-1 GB/T 14048.5 UL 60947-5-1 CSA C22.2 No 60947-5-1 JIS C8201-5-1 |
Product certifications |
CB Scheme CCC UL CSA EAC CE UKCA |
IP degree of protection |
IP2X front face conforming to VDE 0106 |
Protective treatment |
TH conforming to IEC 60068 |
Ambient air temperature for operation |
-40…60 °C 60…70 °C with derating |
Ambient air temperature for storage |
-60…80 °C |
Operating altitude |
0...3000 m |
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Height |
5.000 cm |
Package 1 Width |
9.000 cm |
Package 1 Length |
11.000 cm |
Package 1 Weight |
356.000 g |
Unit Type of Package 2 |
S02 |
Number of Units in Package 2 |
20 |
Package 2 Height |
15.000 cm |
Package 2 Width |
30.000 cm |
Package 2 Length |
40.000 cm |
Package 2 Weight |
7.351 kg |
Unit Type of Package 3 |
P06 |
Number of Units in Package 3 |
320 |
Package 3 Height |
75.000 cm |
Package 3 Width |
80.000 cm |
Package 3 Length |
60.000 cm |
Package 3 Weight |
125.616 kg |
Warranty |
18 months |
Reviews