ABL8RPM24200
SPECIFICATIONS:
Range of product |
Modicon Power Supply |
Product or component type |
Power supply |
Power supply type |
Regulated switch mode |
Nominal input voltage |
100...120 V AC single phase, terminal(s): N-L1 200...240 V AC phase to phase, terminal(s): L1-L2 |
rated power in W |
480 W |
Output voltage |
24 V DC |
Power supply output current |
20 A |
Permissible temporary current boost |
1.5 x In (for 4 s) |
anti-harmonic filter |
Low frequency harmonic currents |
Input voltage limits |
85...132 V AC 170...264 V AC |
Inrush current |
30 A |
Power factor |
0.68 at 240 V AC 0.69 at 120 V AC |
Efficiency |
88 % |
Output voltage adjustment |
24...28.8 V adjustable |
Power dissipation in W |
57.6 W |
Provided equipment |
Power factor correction filter conforming to IEC 61000-3-2 |
Output protection type |
Against overload, protection technology: manual or automatic reset Against overvoltage, protection technology: 30...32 V, manual reset Against short-circuits, protection technology: manual or automatic reset Against undervoltage, protection technology: tripping if U < 21.6 V Thermal, protection technology: automatic reset |
Connections - terminals |
Removable screw terminal block: 2 x 2.5 mm², for diagnostic relay Screw type terminals: 3 x 0.5...3 x 4 mm², (AWG 22...AWG 12) for input connection Screw type terminals: 1 x 0.5...1 x 4 mm², (AWG 22...AWG 12) for input ground connection Screw type terminals: 4 x 0.5...4 x 4 mm², (AWG 22...AWG 12) for output connection |
Status LED |
1 LED (green and red) output voltage 1 LED (green, red and orange) output current |
Depth |
145 mm |
Height |
125 mm |
Width |
146 mm |
Net weight |
1.6 kg |
Output coupling |
Series Parallel |
Marking |
CE |
Mounting support |
35 x 7.5 mm symmetrical DIN rail 35 x 15 mm symmetrical DIN rail |
operating position |
Vertical |
Supply |
SELV conforming to EN/IEC 60950-1 SELV conforming to EN/IEC 60204-1 SELV conforming to IEC 60364-4-41 |
Dielectric strength |
2500 V with between input and ground 3000 V with between input and output 500 V with between output and ground |
Standards |
CSA C22.2 No 60950-1 UL 508 EN/IEC 62368-1 |
Product certifications |
CCSAus EAC KC RCM UL |
Environmental characteristic |
EMC conforming to EN 61000-6-1 EMC conforming to EN 61000-6-3 EMC conforming to EN 55024 EMC conforming to EN/IEC 61000-6-4 EMC conforming to EN/IEC 61204-3 Safety conforming to EN/IEC 60950-1 Safety conforming to EN/IEC 61204-3 |
Operating altitude |
2000 m |
IP degree of protection |
IP20 conforming to EN/IEC 60529 IP10 |
Ambient air temperature for operation |
50…60 °C with derating factor mounting position A < 2000 m -25…50 °C without derating mounting position A < 2000 m |
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Height |
16.084 cm |
Package 1 Width |
17.706 cm |
Package 1 Length |
17.786 cm |
Package 1 Weight |
2.82 kg |
Unit Type of Package 2 |
S04 |
Number of Units in Package 2 |
6 |
Package 2 Height |
30 cm |
Package 2 Width |
40 cm |
Package 2 Length |
60 cm |
Package 2 Weight |
17.6 kg |
Unit Type of Package 3 |
P06 |
Number of Units in Package 3 |
36 |
Package 3 Height |
73.5 cm |
Package 3 Width |
60.0 cm |
Package 3 Length |
80.0 cm |
Package 3 Weight |
101.52 kg |
Warranty |
18 months |
Reviews